Features
SiUS30-604
4
General Information
Because the system is water cooled, the outside air temperature does not affect capacity.
Furthermore, water cooling means no defrost operation is required, so rapid starting assures
quick and comfortable heating in the coldest conditions.
Cold climate capability
General air cooled
air conditioning system
VRV-WII
Level difference
between indoor units:
up to
49 ft
Long refrigerant piping length
Within the refrigerant piping system, up to 390 ft of actual piping length and 164 ft of height
difference between the VRV-WII and indoor units are possible. Water piping does not enter
occupied spaces, so there is no worry of water leaking.
If the VRV-WII is above indoor units. 131 ft if the VRV-WII is below indoor units.
Total heating
capacity(%)
Outside air
temperature
(CDB)
-14.7
100
60
80
-12.6 -10.5
-9.5 -8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
Refrigerant piping
Water piping
VRV-WII
VRV-WII
Level difference
between
the VRV-WII units:
up to
6.5 ft
Level difference between
the VRV-WII and indoor units:
Up to
164 ft
if the VRV-WII is above
Up to
130 ft
if the VRV-WII is below
REFNET Joint
Actual piping length
after piping branch:
up to
130 ft
Standard system (Heat pump type)
*Example only.
• Actual length up to outside unit
branch piping: up to
33 ft
• Equivalent length up to outside
unit branch piping: up to
43 ft
• Actual piping length between the VRV-WII and
indoor units: up to
390 ft
• Equivalent piping length between the VRV-WII
and indoor units: up to
459 ft
• Total piping length between the VRV-WII and
indoor units: up to
980 ft
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...