Field Setting
SiUS30-604
104
Test Operation
External ON/OFF input
This input is used for “ON / OFF operation” and “Protection device input” from the outside. The
input is performed from the T1-T1 terminal of the operation terminal block (X1A) in the electric
component box.
Setting Table
Fan Speed Changeover When Thermostat is OFF
By setting to “Set Fan Speed”, you can switch the fan speed to the set fan speed when the heating
thermostat is OFF.
∗
Since there is concern about draft if using “fan speed up when thermostat is OFF”, you should
take the setup location into consideration.
Setting Table
Auto Restart after Power Failure Reset
For the air conditioners with no setting for the function (same as factory setting), the units will be left
in the stop condition when the power supply is reset automatically after power failure reset or the
main power supply is turned on again after once turned off. However, for the air conditioners with
the setting, the units may start automatically after power failure reset or the main power supply
turned on again (return to the same operation condition as that of before power failure).
For the above reasons, when the unit is set enabling to utilize “Auto restart function after power
failure reset”, utmost care should be paid for the occurrence of the following situation.
F2 T1 T2
Forced stop
Input A
Mode No.
Setting
Switch No.
Setting
Position No.
Operation by input of the signal A
12 (22)
1
01
ON: Forced stop (prohibition of using the remote
controller)
OFF: Permission of using the remote controller
02
OFF
→
ON: Permission of operation
ON
→
OFF: Stop
03
ON: Operation
OFF: The system stops, then the applicable unit
indicates “A0”. The other indoor units indicate “U9”.
Mode No.
First Code No.
Second Code No.
Setting
12 (22)
3
01
LL Fan Speed
02
Set Fan Speed
Caution 1. The air conditioner starts operation suddenly after power failure reset or the
main power supply turned on again. Consequently, the user might be
surprised (with question for the reason why).
2. In the service work, for example, turning off the main power switch during the
unit is in operation, and turning on the switch again after the work is
completed start the unit operation (the fan rotates).
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...