Protection Control
SiUS30-604
74
Function
6.4
Inverter Protection Control
Inverter current protection control and inverter fin temperature control are performed to prevent
tripping due to a malfunction, or transient inverter overcurrent, and fin temperature increase.
∗
This control is carried out in each outside unit.
[Inverter overcurrent protection control]
[Inverter fin temperature control]
Not limited
Inverter current standby
Inverter current < Ia
INV upper limit frequency = 230 Hz
&
Inverter current
> 25.1A for 260 sec. (220V unit)
220-V unit
Ia
26.5 A
• When occurring 3 times within 60 min.,
the malfunction code “L8” is output.
Comp. upper limit down 1 step/15 sec.
Comp. upper limit up 1 step/20 sec.
Inverter current > Ia
Inverter current < Ia
continues for 3 min. or more
Invertercurrent > Ia
Less than 2 times
within 60 min.
Normal operation
Tfin > 122
°
F
Tfin < 86
°
F
Fin temp. standby
Tfin < 174.2
°
F
Compressor up limit frequency = 230 Hz
&
Tfin > 208.4
°
F
• When occurring 3 times within 60 min.,
the malfunction code “L4” is output.
Tfin : Inverter fin temperature
Cooling fan for electric
component box
Comp. upper limit down 1 step/15 sec.
Comp. upper limit up 1 step/1 min.
Tfin
≤
174.2
°
F
for continues 3 min.
Tfin
≥
179.6
°
F
Tfin
≥
179.6
°
F
Less than 2 times
within 60 min.
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...