SiUS30-604
Field Setting
Test Operation
123
f
Set Cool / Heat for More Than One Outside Unit System Simultaneously in Accordance with Unified Master
Outside Unit by Cool/Heat Switching Remote Controller
Add and change the following items to
e
.
★
Install cool/heat switching remote controller on the group master outside unit.
★
Set SS1 on the group master outside unit PC board.
Supplementation on
e
and
f
.
When switching cool/heat for each adapter PC board with the use of more than one adapter PC
board, set the address of the adapter PC board DS1 and DS2 so that it matches the unified cool/
heat address of outside unit PC board.