Troubleshooting by Remote Controller
SiUS30-604
150
Troubleshooting
Malfunction code indication by outdoor unit PCB
<Selection of setting item>
<Confirmation of malfunction 1>
To enter the monitor mode, push the
MODE button (BS1) when in
“Setting mode 1”.
Push the SET button (BS2) and set
the LED display to a setting item.
Push the RETURN button (BS3)
once to display “First digit” of
malfunction code.
<Confirmation of malfunction 2>
Push the SET button (BS2) once to
display “Second digit” of malfunction
code.
Push the RETURN button (BS3) and
switches to the initial status of
“Monitor mode”.
∗
Push the MODE button (BS1) and
returns to “Setting mode 1”.
<Confirmation of malfunction 3>
Push the SET button (BS2) once to
display “master or slave1 or slave2”
and “malfunction location”.
* Refer P.122 for Monitor mode.
* Refer P.122 for Monitor mode.
Detail
description
on next
page.
Contents of malfunction
Malfunction
code
Abnormal discharge pressure
HPS activated
E3
Abnormal suction pressure
Abnormal Pe
E4
Compressor lock
Detection of INV compressor lock
E5
Over load, over current, abnormal lock of
outdoor unit fan motor
Instantaneous over current of DC fan motor
Detection of DC fan motor lock
E7
Malfunction of electronic expansion valve
EV1
E9
EV3
Abnormal position signal of outside unit fan motor Abnormal position signal of DC fan motor
H7
Faulty sensor of outside air temperature
Faulty Ta sensor
H9
Abnormality in water system
HJ
Abnormal discharge pipe temperature
Abnormal Td
F3
Abnormal heat exchanger temperature
Refrigerant over charge
F6
Faulty sensor of discharge pipe temperature Faulty Tdi sensor
J3
Faulty sensor of heat exchanger gas pipe thermistor Faulty Tg sensor
J4
Faulty sensor of suction pipe temperature
Faulty Ts sensor
J5
Faulty sensor of receiver temperature
Faulty Tl sensor
J7
Faulty sensor of subcool heat exchanger temperature Faulty Tsh sensor
J9
Faulty sensor of discharge pressure
Faulty Pc sensor
JA
Faulty sensor of suction pressure
Faulty Pe sensor
JC
Faulty Inverter PC board
Faulty IPM
L1
Faulty Current sensor 1
Faulty Current sensor 2
Abnormal DIPSW setting
Inverter radiation fin temperature rising
Over heating of inverter radiation fin temperature
L4
DC output over current
Inverter instantaneous over current
L5
Electronic thermal switch
Electronic thermal switch 1
L8
Electronic thermal switch 2
Out-of-step
Speed down after startup
Lightening detection
Stall prevention (Limit time)
Stall prevention (Current increasing)
L9
Stall prevention (Faulty startup)
Abnormal wave form in startup
Out-of-step
Transmission error between inverter and
outdoor unit
Inverter transmission error
LC
Open phase/Power supply imbalance
Imbalance of inverter power supply voltage
P1
Faulty temperature sensor inside switch box Faulty thermistor of inverter box
P3
Faulty temperature sensor of inverter
radiation fin
Faulty thermistor of inverter fin
P4
Incorrect combination of inverter and fan driver Incorrect combination of inverter and fan driver
PJ
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...