Troubleshooting (OP: Unified ON/OFF Controller)
SiUS30-604
254
Troubleshooting
In order to maintain low pressure,
frequency decreases due to
capacity control.
Reaches the lowest
frequency
With low outdoor air cooling
control, fan is controlled in
order to maintain high
pressure = Hunting in fact
When frequency reaches the
lowest level, low pressure cannot
be maintained.
High pressure drops as
compressor capacity
decreases.
In order to maintain low
pressure, frequency
decreases due to capacity
control.
Low pressure rises due to
large open degree of indoor
unit electronic expansion
valve. Frequency slightly
increases due to capacity
control.
Frequency decreases due
to droop control.
The open degree of the outside unit
electronic expansion valve increases.
The outside unit electronic
expansion valve opens fully.
Frequency increases. Discharges pipe or low
pressure droop control
Any one of electronic
expansion valves opens fully.
The open degree of the indoor unit
electronic expansion valve increases.
[CHECK 6] Check for inadequate refrigerant quantity
In case of the VRV, judgment must be made based on operation conditions in relation to pressure control and
electronic expansion valve control. Refer to the following criteria to make such decisions.
Diagnosis of inadequate refrigerant
(1) The superheated degree of suction gas increases and temperature of compressor discharge gas
rises.
(2) The superheated degree of suction gas increases and the electronic expansion valve slightly
opens.
(3) With low pressure, cooling capacity (heating capacity) is unavailable.
High pressure
Low pressure
Frequency
Cooling
å~áº
Heating
High pressure
Low pressure
Frequency
Maintains a certain
level of low pressure
Reaches the
lowest frequency
Maintains a certain
level of high
pressure
Adequate level
(Degree of inadequate refrigerant)
Increase in the degree of
inadequate refrigerant
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...