SiUS30-604
Special Operation
Function
81
7.4
Refrigerant Drift Prevention
“Refrigerant drift prevention control” is carried out, in order to prevent refrigerant drift among
outside units during heating operation using outside multiple connection. Excessively charged
refrigerant in outside units are collected and transferred to other outside units that are running out
of gas by controlling the solenoid valve.
(1) In case of cooling/heating changeover connection
When the superheated at the evaporator outlet degree is large, open the solenoid valve (SVG) for
venting receiver gas of the outside units that are running out of gas.
(2) In case of cooling/heating simultaneous connection
When the superheated degree at the evaporator outlet is large, open the solenoid valve (SVG) for
venting receiver gas of the outside units that are running out of gas and the solenoid valve (SVL) for
pressurizing the receiver of the excessively charged outside units.
When the superheated
degree at the evaporator
outlet is large
When the superheated
degree at the evaporator
outlet is small
Normal operation
(SVG=OFF)
SVG=ON
When the superheated
degree at the evaporator
outlet is large
When the superheated
degree at the evaporator
outlet is small
Normal operation
(SVG=OFF)
(SVL=OFF)
SVG=ON
SVL=ON
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...