SiUS30-604
Troubleshooting by Indication on the Remote Controller
Troubleshooting
163
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Provide 208~230V power
supply.
YES
NO
Is power supply
208~230V provided?
Replace the limit switch
connecting cable.
Replace indoor unit PC board.
Replace the power supply
connecting cable.
Replace swing motor.
Take the cam mechanism
apart, reassemble and turn on
again.
YES
NO
YES
YES
NO
YES
NO
Connect the connector to X9A
and turn on again.
Replace indoor unit PC board.
NO
NO
YES
NO
YES
NO
YES
YES
NO
Indoor unit
is a model equipped
with a swing flap
function
The swing
motor works when
the power supply is turned
off and then back
on.
When
the air flow
direction flap’s cam
mechanism is disconnected
from the swing motor,
operation is normal
when turned
on again.
The connecting cable
has no continuity.
After
turning
the swing-flap
ON and then
stopping with the
remote controller, the
voltage of X6A of the indoor
unit PC board is 208 ~ 230V
when turnedon
again (within 30
seconds of
turning on
again).
The connector
is connected to X9A of
the indoor unit PC
board.
The limit switch
functions normally.
The connecting
cable is short-circuited
or disconnected.
Replace swing motor.
(V2780)
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...