Troubleshooting by Indication on the Remote Controller
SiUS30-604
220
Troubleshooting
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(V2826)
The “U4”
display blinks on
the remote controllers of
other units within the same
refrigerant
system.
Refer to failure diagnosis for “U5”
malfunction code.
Re-diagnose by display after
passage of 2 minutes or more.
NO
NO
Refer to failure diagnosis for “U4”
malfunction code.
YES
YES
“U9”
has been displayed for 2
minutes or more.
NO
Turn on all indoor units.
Refer to failure diagnosis for “A1”
malfunction code.
NO
YES
The “A1”
display blinks on
the remote controllers of
other units within the same
refrigerant
system.
Refer to failure diagnosis for “UA”
malfunction code.
YES
The “UA”
display blinks on the
remote controllers of other
units within the same
refrigerant
system.
Refer to failure diagnosis for “A9”
malfunction code.
NO
YES
The “A9”
display blinks on
the remote controllers of
other units within the same
refrigerant
system.
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...