SiUS30-604
Troubleshooting by Indication on the Remote Controller
Troubleshooting
211
Troubleshooting
YES
YES
NO
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
YES
Replace the inverter PCB
(A2P).
If the inverter PCB is
significantly damaged,
the compressor or the
fan motor may be
damaged as well.
The inverter PCB
(A2P) is damaged.
The "U2" malfunction
recurs.
The compressor
enters standby mode
without completing the
startup sequence.
Connect and disconnect the
following connectors.
X4A (A2P)
↔
X25A (A1P)
X6A (A2P)
↔
X33A (A1P)
Turn ON the power supply, and
then set the RUN switch to ON.
Replace the inverter PCB
(A2P).
If the inverter PCB is
significantly damaged,
check for the
compressor.
Check for every wire
connection.
Continue the compressor
operation.
It is supposed that the
faulty power supply
results from external
causes such as
instantaneous power
failure.
YES
YES
NO
NO
YES
Check for the power supply
conditions.
Does the voltage fall in the
range of 208 to 230V±10%?
Is there any open phase or
erroneous wire connection?
Does the unbalanced voltage
fall within 6V?
Any of the
conditions aforementioned
is defective.
The compressor
has an insulation resistance
of 100k
Ω
or less.
Remedy the defective
conditions.
Replace the compressor.
Replace the inverter PCB
(A2P).
Is the
power transistor normal?
∗
∗
Power transistor check: Refer page 281.
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...