Troubleshooting by Indication on the Remote Controller
SiUS30-604
214
Troubleshooting
Troubleshooting
(V2822)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is
indoor - outside unit
and outside unit - outside unit
transmission wiring
normal?
Supply 208~230 V.
Replace the fuse.
Fix the indoor/outside unit
transmission wiring.
Push and hold the RESET
button on the outside unit PC
board for 5 seconds.
Replace the outside unit PC
Board (A1P).
YES
YES
NO
YES
Replace the indoor unit PC
Board.
Push and hold the RESET
button on the master outside
unit PC Board for 5 seconds.
Fix the indoor/outside unit
transmission wiring.
YES
NO
NO
YES
Has
the indoor
or outside unit PC
board been replaced,
or has the indoor - outside
or outside - outside unit
transmission wiring
been
modified?
All
indoor unit
remote controllers of the
same refrigerant system
display
“U4”.
NO
Outside
unit PC board
microcomputer monitor
(HAP) blinks.
NO
NO
NO
Operation
ready lamp (H2P) is
blinking.
Lamp does
not go off for 12 minutes
or more.
Is indoor
- outdoor and outside -
outside unit transmission
wiring normal?
YES
The fuse on
the outside unit’s PC
board is burnt.
Replace the transformer.
replacement
Replace outside unit PC
board. (A1P)
NO
The
secondary voltage
of the transformer is
about 22 V.
NO
The
voltage between
terminals L1, L2 and L3
of X1M terminal
is 208~230 V.
∗
The unit will not operate for
up to 12 minutes.
Reset the power supply.
YES
YES
YES
NO
YES
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...