Troubleshooting by Indication on the Remote Controller
SiUS30-604
196
Troubleshooting
2.29
“
L4
”
Outside Unit:
Malfunction of Inverter Radiating Fin
Temperature Rise (R1T)
Remote
Controller
Display
L4
Applicable
Models
RWEYQ60, 72, 84MTJU
Method of
Malfunction
Detection
Fin temperature is detected by the thermistor of the radiation fin.
Malfunction
Decision
Conditions
When the temperature of the inverter radiation fin increases above 98°C.
Supposed
Causes
Actuation of fin thermal (Actuates above 98°C)
Defect of inverter PC board
Defect of fin thermistor
Troubleshooting
∗
2: Refer to thermistor resistance / temperature characteristics table on P278.
(V2811)
Resistance
check of the radiator fin
thermistor
Defect of power unit radiation.
•
Intake port is clogged
•
Radiator fin is dirty
•
Outdoor temperature is high
NO
Replace the thermistor.
YES
Abnormal
Is reset possible?
Reset and operate.
Normal
Replace the inverter PC board
NO
YES
Temperature
of the radiator fin rises.
Actuates at min.
208
°
F
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...