Troubleshooting by Error Codes
SiUS281811EA
234
Part 6 Service Diagnosis
4.16 Electronic Expansion Valve Coil Abnormality, Dust
Clogging
Error Code
A9
Applicable
Models
All indoor models
Method of Error
Detection
Electronic expansion valve coil conditions are checked via microcomputer.
The electronic expansion valve main body is checked for dust clogging via microcomputer.
Error Decision
Conditions
Pin input for electronic expansion valve coil is abnormal when initializing microcomputer.
Either of the following conditions is seen/caused/occurs while the unit stops operation.
R1T – R2T > 8°C (14.4°F)
R2T shows fixed degrees or below.
R1T: temperature of suction air
R2T: temperature of liquid pipe of heat exchanger.
Supposed
Causes
Defective electronic expansion valve coil
Defective indoor unit main PCB
Defective relay cables