Servicing Items to be Confirmed
SiUS281811EA
198
Part 6 Service Diagnosis
(4) Precautions for piping work and refrigerant charging:
This unit uses R-410A refrigerant. Pay attention to the following conditions.
1. The charging pipe and the manifold tube use R-410A products for pressure maintenance and
avoiding contamination by impurities (SUNISO oil, etc.).
2. Be sure to purge with nitrogen when brazing.
Properly perform airtightness test and vacuum drying. (Airtight test pressure: 4.0 MPa (580
psi))
Charge refrigerant in liquid state.
(5) Precautions for operating in servicing mode (field setting):
When a test operation is interrupted or after exiting service mode, please wait for at least one
minute before entering service mode again. In case of continuous execution, the outdoor unit PCB
may sometimes display an error code. If any error codes are displayed, press the
RETURN (BS3)
button. If performing the above operation still does not eliminate the error, reconnect the unit to the
power supply.
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...