
SiUS281811EA
Troubleshooting by Error Codes
Part 6 Service Diagnosis
235
Reference
Troubleshooting
CHECK 18
Refer to page 308.
NO
NO
NO
YES
YES
Shut the power supply OFF after
connection and then restart.
Replace the electronic expansion
valve coil.
Replace the relay cables.
When restarting the operation after
shutting the power supply OFF
does not work, replace the indoor
unit main PCB (A1P).
NO
Replace the electronic expansion
valve main body.
Power is supplied.
YES
YES
Electronic
expansion valve is
connected to X7A
of indoor unit
PCB.
Relay cables short
circuit or
disconnected.
Check
of electronic
expansion valve coil
indicates normal.
CHECK 18
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...