SiUS281811EA
Field Setting from Remote Controller
Part 5 Field Settings and Test Operation
155
Note(s)
: Factory setting
When the 10 (20)-6 setting is changed to
02
, several indoor units are controlled by one remote
controller thermistor, so note that the room temperature might be uneven.
1.5.3 Filter Cleaning Sign
Whether or not to display
Filter Cleaning
after operation of a certain duration can be selected.
: Factory setting
∗
Filter Cleaning
is not displayed when an Auto-clean Panel is connected.
1.5.4 Time for Absence Area Detection
(For units with an infrared presence sensor)
By selecting the energy-saving operation mode when absent, the target temperature is shifted to
the energy-saving end by 1°C (1.8°F) (maximum 2°C (3.6°F)) after the state of absence continues
for a certain period of time.
Absent time defined for detection can be selected as follows:
: Factory setting
The set temperature displayed on the remote controller remains the same even if the target
temperature is shifted.
As soon as people are detected while the temperature is shifted, this control will be cancelled
(reset).
Mode No.
First Code No.
Second Code No.
Contents
10 (20)
6
01
Remote controller thermistor control is not
permitted during group control
02
Remote controller thermistor control is
permitted during group control
Mode
No.
First Code No. Second Code
No.
Contents
10 (20)
3
01
Displayed
02
Not displayed
Mode
No.
First Code No. Second Code
No.
Contents
10 (20)
7
01
30 minutes
02
60 minutes
30 (60)
∗
60 (120)
∗
31
(°C)
19
28
27
26
17
21
30
29
20
18
87.8
(°F)
66.2
82.4
80.6
78.8
62.2
69.8
86
84.2
68
64.4
Elapsed time of absence (min.)
Set temperature
Human detection
Cooling (at 28°C (82.4°F))
Heating (at 20°C (68°F))
State of absence
∗
The values in parentheses represent the time
when Second code No. is
02
.
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...