![background image](http://html1.mh-extra.com/html/daikin/skyair-rzr-ta-series/skyair-rzr-ta-series_service-manual_3918999126.webp)
Protection Control
SiUS281811EA
120
Part 4 Functions and Control
4.3 Discharge
Pipe
Temperature Protection Control
This discharge pipe temperature protection control is used to protect the compressor internal
temperature against an error or transient increase of discharge pipe temperature.
HTdi: Value of inverter compressor discharge pipe temperature (Tdi) compensated with outdoor air
temperature
Tp: Value of compressor port temperature calculated by Tc, Te, and suction superheated degree.
•
HTdi > 115˚C (239˚F)
•
Tp > 135˚C (275˚F)
OR
36 Hz Unload
•
HTdi > 115˚C (239˚F)
•
Tp > 135˚C (275˚F)
OR
•
HTdi > 135˚C (275˚F)
•
HTdi > 120˚C (248˚F) for 10 minutes or more.
OR
•
HTdi < 110˚C (230˚F)
•
Tp < 125˚C (257˚F)
&
After 30 seconds
After 20 seconds
•
HTdi > 130˚C (266˚F)
•
HTdi > 120˚C (248˚F)
for 90 seconds
or more.
OR
•
HTdi < 100˚C (212˚F)
•
Tp < 110˚C (230˚F)
&
Discharge pipe
temperature standby
Discharge pipe protection
control not limited
Compressor upper limit
frequency: 1-step down from
current compressor frequency
In discharge pipe temp.
protection control
When occurring 3 times within 100 minutes,
the error code
F3
is output.
Compressor upper limit frequency: 1-step
up from current compressor frequency
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...