SiUS281811EA
Troubleshooting by Error Codes
Part 6 Service Diagnosis
231
Note(s)
Troubleshooting
∗
1. Connector and indoor unit PCB
Connect correctly.
Is the
connector (
1)
correctly connected?
NO
YES
Connect correctly.
Is
the limit
switch's connector
(
2) correctly
connected?
NO
Replace the indoor unit PCB.
Replace the indoor unit PCB.
208-230 VAC?
NO
YES
Does the
swing flap motor swing?
Does
continuity/no continuity
reverse?
NO
NO
Turn the power supply OFF
once and back ON, and check
whether the swing flap motor
swings when the power
supply is turned back ON.
Turn the power supply OFF
once and restart, and measure
the output voltage of connector
(
3) when the power supply is
restarted.
Disconnect the connector
(
2), turn the power supply
OFF once and restart, and
check if the limit switch has
continuity when the power
supply is restarted.
YES
YES
Replace the swing flap motor.
YES
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution
Model
Connector for swing flap motor
PCB
∗
1
∗
2
∗
3
FHQ
X6A, X9A
X9A
X6A
A1P
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...