Field Settings from Outdoor Unit
SiUS281811EA
174
Part 5 Field Settings and Test Operation
The numbers in the No. column represent the number of times to press the
SET
(
BS2
) button.
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
Factory setting
1
Cool / heat
unified address
k
h
h
h
h
h
k
Address
0
k h h h h h h
Binary number
1
k h h h h h k
~
)
s
t
i
g
i
d
6
(
31
k h k k k k k
2
Low noise / demand
address
k
h
h
h
h
k
h
Address
0
k h h h h h h
Binary number
1
k h h h h h k
~
)
s
t
i
g
i
d
6
(
31
k h k k k k k
3
Test operation settings
k
h
h
h
h
k
k
Test operation : OFF
k h h h h h k
Test operation : ON
k h h h h k h
5
Indoor unit forced fan H
k
h
h
h
k
h
k
Normal operation
k h h h h h k
Indoor forced fan H
k h h h h k h
6
Indoor unit forced
operation
k
h
h
h
k
k
h
Normal operation
k h h h h h k
Indoor forced operation
k h h h h k h
8
Te setting
k
h
h
k
h
h
h
Target Te: 11°C (51.8°F)
k h h h k k k
10°C (50°F)
k h h h k k h
9°C (48.2°F)
k h h h k h k
8°C (46.4°F)
k h h h k h h
Variable (VRT)
k h h h h k k
6°C (42.8°F)
k h h h h k h
3°C (37.4°F)
k h h h h h k
9
Tc setting
k
h
h
k
h
h
k
Target Tc: 52°C (125.6°F)
k h h h k h h
46°C (114.8°F)
k h h h h k h
Variable (VRT)
k h h h h h k
10
Defrost changeover
setting
k
h
h
k
h
k
h
Earlier start defrost
k h h h k h h
Normal (factory setting)
k h h h h k h
Later start defrost
k h h h h h k
12
External low noise /
demand setting
k
h
h
k
k
h
h
External low noise/demand:
NO
k h h h h h k
External low noise/demand:
YES
k h h h h k h
13 AIRNET address
k
h
h
k
k
h
k
Address
0
k h h h h h h
Binary number
1
k h h h h h k
~
)
s
t
i
g
i
d
6
(
63
k k k k k k k
16
Setting of heat pump
lockout 1
k
h
k
h
h
h
h
OFF
k h h h h h k
ON
k h h h h k h
19
Emergency automatic
heat pump lockout
k
h
k
h
h
k
k
OFF
k h h h h h k
ON
k h h h h h h
20
Additional refrigerant
charge operation setting
k
h
k
h
k
h
h
Refrigerant charging: OFF
k h h h h h k
Refrigerant charging: ON
k h h h h k h
21
Refrigerant recovery /
vacuuming mode setting
k
h
k
h
k
h
k
Refrigerant recovery /
vacuuming: OFF
k h h h h h k
Refrigerant recovery /
vacuuming: ON
k h h h h k h
22
Night-time low noise
setting
k
h
k
h
k
k
h
OFF
k h h h h h h
Level 1 (outdoor fan with 6 step or lower)
k h h h h h k
Level 2 (outdoor fan with 5 step or lower)
k h h h h k h
Level 3 (outdoor fan with 4 step or lower)
k h h h h k k
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...