SiUS281811EA
Field Setting from Remote Controller
Part 5 Field Settings and Test Operation
149
1.4 List of Field Settings for Indoor Unit
: Factory setting
Mode
No.
(
∗
2)
First
Code
No.
Description
Second Code No.
Page
Reference
01
02
03
04
10 (20)
0
Filter
cleaning
sign interval
Ultra long life
filter
Light
Approx.
10,000
hrs.
Heavy
Approx.
5,000
hrs.
—
—
Long life filter
Approx.
2,500
hrs.
Approx.
1,250
hrs.
Standard filter
Approx.
200
hrs.
Approx.
100 hrs.
0 (
∗
8) Filter sign setting
Light
Heavy
—
—
1
Filter type
Long life filter
Ultra long life filter
—
—
1 (
∗
8) Filter cleaning sign interval
Short interval
Long interval
—
—
2
Remote controller thermistor
Remote
controller
ther
Suction air
thermistor
Only suction air
thermistor
Only remote
controller
thermistor
—
2 (
∗
8)
Remote sensor and remote
controller thermistor
—
Only remote
sensor thermistor
Only remote
controller
thermistor
—
3
Filter cleaning sign
Displayed
Not displayed
—
—
6
Remote controller thermistor
control during group control
Not permitted
Permitted
—
—
7 (
∗
6) Time for absence area
detection
30 minutes
60 minutes
—
—
11 (21)
1 (
∗
8) Auxiliary electric heater ON
temperature: Ton
Refer to the page on the right for details.
1
Auxiliary electric heater
ON/OFF temperature: Ton/Toff
2 (
∗
8) Auxiliary electric heater OFF
temperature: Toff
3
Setting of airflow rate when
heating
Standard
Slightly increased
Increased
—
3 (
∗
8) Electric heater setting
Refer to the page on the right for details.
5 (
∗
8) Electric heater capacity setting
Refer to the page on the right for details.
6 (
∗
6)
Setting the rate of human
detection
High sensitivity
Low sensitivity
Standard
sensitivity
Infrared
presence
sensor
disabled
7
Automatic airflow adjustment
OFF
Completion of
airflow adjustment
Start of
airflow
adjustment
—
8 (
∗
6)
Compensating the temperature
around people
Suction air
temperature only
Priority given on
the suction air
temperature
Standard
Priority given
on the floor
temperature
9 (
∗
6) Compensating the floor
temperature when heating
–4°C (–7.2°F)
–2°C (–3.6°F)
0°C (0°F)
2°C (3.6°F)
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...