Outline of Control (Indoor Unit)
Part 4 Functions and Control
127
6.2.2 With Optional Infrared Presence/Floor Sensor
Whether the thermostat is turned ON or OFF is determined by the difference between the remote
controller set temperature and the detected temperature around people.
• Normal operation
· Cooling operation
· Heating operation
• Dry operation
· When Tro
≤
24.5°C (76.1°F)
· When Tro > 24.5°C (76.1°F)
∗
: Description of symbols
Δ
T = Detected room temperature – Remote controller set temperature
Tro: Detected room temperature at the start of dry operation
Tr: Determined by the room temperature detected by the thermistor
Control range of temperature around people
When the floor temperature is very low, operation using the temperature around people may cause
the suction air temperature to operate outside of use range.
To avoid the above condition, a limit based on the suction air temperature is set for the use range of
the temperature around people.
Cooling operation
When the floor temperature is lower than suction air temperature (R1T), R1T will be treated
as the control target temperature for operation.
When the temperature around people is 15°C (59°F) or lower, R1T will be treated as the
control temperature for operation.
Heating operation
When the floor temperature is higher than suction air temperature (R1T), R1T will be treated
as the control target temperature in operation.
When the temperature around people is 33°C (91.4°F) or higher, R1T will be treated as the
control temperature for operation.
Thermostat OFF
Normal operation
(Thermostat ON)
Δ
T
≤
–1.0˚C (–1.8˚F)
Δ
T
≥ +
1.0˚C (
+
1.8˚F)
Thermostat OFF
Normal operation
(Thermostat ON)
Δ
T
≥ +
1.0˚C (
+
1.8˚F)
Δ
T
≤
–1.0˚C (–1.8˚F)
Thermostat OFF
Dry operation
Tr < Tro – 1.0˚C (–1.8˚F)
Tr > Tro + 1.0˚C (+1.8˚F)
Thermostat OFF
Dry operation
Tr < Tro – 1.5˚C (–2.7˚F)
Tr > Tro + 1.5˚C (+2.7˚F)
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...