SiUS281811EA
Field Setting from Remote Controller
Part 5 Field Settings and Test Operation
167
1.5.36 Setback Availability
For BRC1E series only
Select the operation mode in which the setback function is available.
: Factory setting
1.5.37 Setting Restricted/Permitted for Airflow Block
For Sensing flow type only
The airflow block function cannot be enabled when closure material kit, fresh air intake kit,
separately installed natural evaporation type humidifier, or branch air duct is equipped, due to
the possibility of dew condensation.
This setting restricts the airflow block function, preventing that the airflow block is inadvertently set
to ON.
Ensure that “Airflow block restricted” is set when using the options listed above.
: Factory setting
Mode
No.
First Code
No.
Second Code
No.
Contents
1e
2
01
N/A
02
Heat only
03
Cool only
04
Cool/heat
Mode
No.
First
Code No.
Second
Code No.
Contents
1e
14
01
Airflow block permitted
02
—
03
—
04
—
05
Airflow block restricted
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...