Check
SiUS281811EA
308
Part 6 Service Diagnosis
5.14 Electronic Expansion Valve Coil Check
CHECK 18
Measure the connector pin-to-pin resistance and make sure that the resistance value is within the
range listed in the table below.
FCQ-TA, FTQ-TA
FBQ-P, FAQ-TA
Orange 1
Red 2
Yellow 3
Black 4
— 5
Gray 6
Measuring points
Judgment criteria
1 - 6
35-55
Ω
2 - 6
3 - 6
4 - 6
White 1
Yellow 2
Orange 3
Blue 4
Red 5
Brown 6
Measuring points
Judgment criteria
1 - 3
300
Ω
1 - 5
150
Ω
2 - 4
300
Ω
2 - 6
150
Ω