![background image](http://html1.mh-extra.com/html/daikin/skyair-rzr-ta-series/skyair-rzr-ta-series_service-manual_3918999182.webp)
Field Settings from Outdoor Unit
SiUS281811EA
176
Part 5 Field Settings and Test Operation
The numbers in the No. column represent the number of times to press the
SET (BS2)
button.
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory setting
50
Auxiliary heater
maximum allowable
temperature
k
k
k
h
h
k
h
–17.7°C (0°F)
k h h h h h h
–15°C (5°F)
k h h h h h k
–12.2°C (10°F)
k h h h h k h
–9.4°C (15°F)
k h h h h k k
–6.6°C (20°F)
k h h h k h h
–3.8°C (25°F)
k h h h k h k
–1.1°C (30°F)
k h h h k k h
1.6°C (35°F)
k h h h k k k
∗
4.4°C (40°F)
k h h k h h h
7.2°C (45°F)
k h h k h h k
10°C (50°F)
k h h k h k h
12.7°C (55°F)
k h h k h k k
15.5°C (60°F)
k h h k k h h
18.3°C (65°F)
k h h k k h k
Auxiliary heater always not allowed
k h h k k k h
Auxiliary heater always allowed
k h h k k k k
56
Auxiliary heater
maximum allowable
temperature release
differential
k
k
k
k
h
h
h
2.8°C (5°F)
k h h h h h h
5.6°C (10°F)
k h h h h h k
∗
8.3°C (15°F)
k h h h h k h
57
Heat pump lockout
temperature
k
k
k
k
h
h
k
–26.1°C (–15°F)
k h h h h h h
∗
–23.3°C (–10°F)
k h h h h h k
–20.5°C (–5°F)
k h h h h k h
–17.7°C (0°F)
k h h h h k k
–15°C (5°F)
k h h h k h h
–12.2°C (10°F)
k h h h k h k
–9.4°C (15°F)
k h h h k k h
–6.6°C (20°F)
k h h h k k k
–3.8°C (25°F)
k h h k h h h
–1.1°C (30°F)
k h h k h h k
1.6°C (35°F)
k h h k h k h
4.4°C (40°F)
k h h k h k k
7.2°C (45°F)
k h h k k h h
10°C (50°F)
k h h k k h k
Forced heat pump lockout
k h h k k k h
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...