Troubleshooting by Error Codes
SiUS281811EA
246
Part 6 Service Diagnosis
4.26 Infrared Presence/Floor Sensor Error
Error Code
CE
Applicable
Models
FCQ-TA
Method of Error
Detection
The contents of a failure vary with the detailed error code. Check the code and proceed with the
flowchart.
Error Decision
Conditions
Error is detected based on sensor output signals
Supposed
Causes
Defective or disconnected infrared presence sensor connector:
CE-01
Defective infrared floor sensor (Temperature compensation circuit disconnection):
CE-02
Defective infrared floor sensor (Temperature compensation short circuit):
CE-03
Defective infrared floor sensor element:
CE-04
Troubleshooting
See diagnosis procedure 2.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Error code
CE-02
See diagnosis procedure 3.
Error code
CE-03
See diagnosis procedure 4.
Error code
CE-04
Error type varies according
to error code. Check the
error code and take the
following steps.
See diagnosis procedure 1.
Error code
CE-01
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...