6.10.2 Heat Pump Lockout Control
For heating operation, users can select to use electric heater. For this, signals are sent using ABC
terminal of outdoor unit PCB.
When the hot-water heating signal is received from the outdoor unit PCB, heating operation is
performed only with the electric heater as manual backup operation. The ON/OFF conditions for
the electric heater are shown below.
Thermostat OFF/Operation OFF
ENTRY/
5 minutes timer starts.
• Condition A
• Time up (
∗
2)
&
H/P Heating: Not in operation
Heater 1: ON
Heater 2: OFF
Fan: ON
Entry/
5 minutes timer starts.
&
OR
• Thermostat step 2: OFF
H/P Heating: Not in operation
Heater 1: ON
Heater 2: ON
(OFF for single heater)
Fan: ON
• Electric heater capacity setting:
Setting not available
• Thermostat step 2: ON
• Time up
• Electric heater capacity
setting: Setting available
Not
Condition A
Not
Condition A
&
Condition A
OR
Condition B: Heater backup prohibiting conditions (
∗
1)
•
Heating or automatic heating mode
•
Thermostat step 1: ON
•
No fan motor system error
•
Hot-water heater: 1 (ON)
•
Heater backup prohibiting conditions (
∗
1) not met
(Not Condition B)
•
Indoor unit error (Abnormal stop)
•
Indoor unit error (Remote controller thermistor error)
•
Indoor unit error (Remote sensor error)
•
Electric heater capacity setting: 01 (No heater kit)
∗
1: The heater backup prohibiting conditions are prioritized. Even when the heater ON
conditions are met, the heater is turned OFF when the prohibiting conditions are met.
∗
2: When the remote controller is ON, Time-up will be set to the initial value.
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...