SiUS281811EA
Check
Part 6 Service Diagnosis
307
FBQ-P
Outdoor Unit
(1) Turn OFF the power supply.
(2) Remove the connector (X106A, X107A) on the PCB to measure the resistance value.
Judgment criteria: resistance value between each phase is within ±20%
(1) Measurement of power wire connector.
Remove the X1A connector from the fan PCB (A2P) and measure the resistance
between the U and V, V and W, and W and U phases of the motor connector (with
five conductors) and check that each phase are balanced (within a permissible
dispersion range of ±20%).
(2)
Measurement of signal wire connector.
Remove the X2A connector and measure the resistance between GND and Vcc,
Hw, Hv, or Hu terminals of the motor connector (with five conductors).
5 Gray
4 Pink
3 Orange
2 Blue
1 Yellow
GND
Vcc
Hw
H
V
H
U
5 Red
4 —
3 White
2 —
1 Black
U
V
W
Connector power wire use (X1A)
Connector signal wire use (X2A)
1 White
2 Orange
3 Brown
4 Blue
5 —
6 —
7 Red
FG
Vsp
Vcc
GND
—
—
Vdc
Connector for signal wires
(X106A, X107A)
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...