SiUS281811EA
Outline of Control (Indoor Unit)
Part 4 Functions and Control
139
Note(s)
&
&
OR
Condition A
•
Heater ON permission (Defrost/oil return): 1 (
∗
4)
&
Condition B
Condition C
•
No fan motor system error
•
High pressure condition: ON (
∗
1)
•
Liquid pipe temperature condition: ON (
∗
2)
•
Heater ON permission (Defrost/oil Return): 0 (
∗
4)
•
Not during defrost/oil return
•
No fan motor system error
•
During defrost/oil return
•
Heater ON permission (Defrost/oil return): 1 (
∗4
)
OR
•
Not during defrost/oil return
•
Fan motor system error
•
Heater ON permission (Defrost/oil return): 0 (
∗4
)
∗
1:
High pressure condition
∗
2:
Liquid pipe temperature condition
∗
3:
Auxiliary heater enabled
∗
4:
Heater ON permission (Defrost/oil return)
∗
5:
Field setting 11 (21)-5. Refer to page 157.
∗
6:
Refer to page 157.
ON
OFF
49
120.2
54
129.2
Tc
(˚C)
(˚F)
ON
OFF
46
114.8
49
120.2
TH2
(˚C)
(˚F)
1:
&
•
Electric heater setting (Field setting 11 (21)-3): 2, 4, 6, 8, 10, 12 (
∗
6)
•
Electric heater capacity setting
≠
01
0: Other than the above
1: Electric heater setting (Field setting 11 (21)-3): 8, 10, 12 (
∗
6)
0: Electric heater setting (Field setting 11 (21)-3): 2, 4, 6 (
∗
6)
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...