Troubleshooting by Error Codes
SiUS281811EA
268
Part 6 Service Diagnosis
4.40 Radiation Fin Temperature Rise Abnormality
Error Code
L4
Applicable
Models
All outdoor units
Method of Error
Detection
The radiation fin temperature is detected by the radiation fin thermistor.
Error Decision
Conditions
The radiation fin temperature exceeds a certain temperature.
Supposed
Causes
Activation of radiation fin thermistor
Defective outdoor main PCB
Defective radiation fin thermistor
Troubleshooting
Defective radiation from the power
unit
• Blocked air suction port
• Stained radiation fin
• High outdoor air temperature
Connect correctly.
Go to
P4
troubleshooting.
Keep operating.
Replace the outdoor main
PCB (A1P).
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution
YES
YES
YES
YES
NO
NO
NO
NO
Is the radiator fin
temperature greater than the
designed temperature?
Does the remote
controller display error code
P4
?
Does the
connector X111A of fin
thermistor connect to the
outdoor unit PCB
correctly?
When the unit starts
operating, is the error code
L4
displayed again?
Connect to the power.
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...