Field Settings from Outdoor Unit
Part 5 Field Settings and Test Operation
183
2.9 Check
Operation
To prevent any trouble in the period of installation on site, the system is provided with a test
operation mode enabling check for incorrect wiring, stop valve left in closed, coming out (or
misplacing with suction pipe thermistor) or discharge pipe thermistor and judgment of piping length,
refrigerant overcharging, and learning for the minimum opening degree of electronic expansion
valve.
Unit stopping
Press the
TEST
button for 5 seconds.
10 seconds to 10 minutes
LED display (H1P~H7P) (
k
:
ON
h
:
OFF
l
:
BLINK)
h h k h h h h
h l h h h h k
Pressure equalizing
Step 1
20 seconds to 2 minutes
10 minutes
3 minutes
15 minutes
h l h h h k h
Cooling start control
Step 2
h l h h h k k
h l h h k k k
Stability waiting operation
Step 3
Refrigerant overcharge judgment
Step 7
•
Stop valve close check
•
Wrong wiring check
•
Piping length check
h l h h k h h
h l h h k h k
h l h h k k h
Judgment function
Step4~6
5 seconds
h l h k h h k
h l h k h k h
Pump down residual operation
Step 8
2 minutes
Standby for restarting
Completion
Step 9
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...