Check
SiUS281811EA
294
Part 6 Service Diagnosis
Note(s)
5.3 Superheat Operation Check
CHECK 3
Referring to the Fault Tree Analysis (FTA) shown below, probe the defective points.
Abnormal piping length
Bent or crushed pipe
(Including moisture choke)
Stop valve closed.
Defective valve coil
Defective valve body
Defective valve coil
Defective valve body
←Are the coil resistance and insulation normal?
←Refer to
CHECK 7
.
←Does the piping length fall in the permissible range?
←Conduct visual checks.
←Eliminate moisture by vacuum operation. (Refer to
CHECK 8
.
)
←Check if the stop valve is open.
Defective
discharge
pipe
temperature
control
Defective hot
gas bypass
control
Hot gas circuit clogging
Defective solenoid
valve coil
Defective solenoid
valve body
Defective service
monitor PCB
Defective main
PCB
Defective valve coil
Defective low
pressure sensor
Defective subcooling
heat exchanger outlet
thermistor
Defective valve
body
Defective
subcooling
electronic
expansion
valve control
Superheat due to
shaft damage
Superheat due to
defective compressor
Defective indoor
unit electronic
expansion valve
Defective
control
Defective
control
Defective
outdoor unit
electronic
expansion valve
Defective four
way valve
operation
[In cooling only]
(
*
1)
(
*
2)
Compressor
overheat
Refrigerant
shortage
High pipe
resistance
Defective
superheated
degree
control.
[In cooling]
If the indoor unit
electronic
expansion valve is
throttled too much:
(
*
3)
[In heating]
If the outdoor unit
electronic
expansion valve
excessively
throttled: (
*
4)
Temperature
increase of
discharge
pipe
Defective
subcooling
electronic
expansion
valve
←Are the coil resistance and
insulation normal?
←Is the connector properly connected?
Are the thermistor resistance characteristics
normal?
←Are the voltage characteristics normal?
←Is the pressure value checked with the
Service Checker corresponding to the
measurement value of the pressure sensor?
←Check if the piping temperature connected
to the four way valve is normal.
Four way valve is in the
middle position.
Leak from hot gas bypass
valve
Defective
control
Defective gas pipe
thermistor of indoor unit
Defective thermistor for
indoor unit liquid pipe
Defective main
PCB
Defective low pressure
sensor
Defective suction pipe
thermistor
Defective main
PCB
←Are the voltage characteristics normal?
←Is the pressure value checked with the Service
Checker corresponding to the measurement
value of the pressure sensor?
←Is the connector properly connected?
Are the thermistor resistance characteristics normal?
←Is the connector properly connected?
Are the thermistor resistance characteristics normal?
←Are the coil resistance and insulation normal?
←Are the coil resistance and insulation normal?
←Is the connector properly connected?
Are the thermistor resistance characteristics normal?
∗
1: Refer to Low pressure protection control on page 118.
∗
2: Refer to Subcooling electronic expansion valve control on page 108.
∗
3: Superheating temperature control in cooling is conducted by indoor unit electronic
expansion valve.
∗
4: Superheating temperature control in heating is conducted by outdoor unit electronic
expansion valve.
∗
5: Judgment criteria of superheat operation: (1) Suction gas superheated degree: 10°C
(18°F) and over. (2) Discharge gas superheated degree: 45°C (81°F) and over, except
immediately after compressor starts up or is running under dropping control.
(Use the above values as a guide. Depending on the other conditions, the unit may be
normal despite the values within the above range.)
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...