Field Settings from Outdoor Unit
SiUS281811EA
170
Part 5 Field Settings and Test Operation
2.2 Setting Mode and Monitor Mode
The following 3 modes can be changed over with the button switches on the PCB and you can find
the present mode by the status of the H1P indicator.
(1) Setting mode 1 (H1P OFF)
Initial status (normal) : Also indicates during abnormal.
(2) Setting mode 2 (H1P ON)
Used to modify the operating status and to set program addresses, etc. Usually used in servicing
the system.
(3) Monitor mode (H1P blinks)
Used to check the program made in setting mode 2.
H1P H3P
H5P H7P
H2P H4P H6P
BS1
(MODE)
BS2
(SET)
BS4
(TEST)
BS5
(RESET)
BS3
(RETURN)
Contents display
Monitor mode
Press the
RETURN (BS3)
button.
Press the
RETURN (BS3)
button.
Setting mode 2
Press the
RETURN (BS3)
button.
Press the
RETURN (BS3)
button.
Press the
RETURN (BS3)
button.
Press the
MODE (BS1)
button.
Press the
MODE (BS1)
button.
Press the
MODE (BS1)
button.
Select a setting condition
with the
SET (BS2)
button.
Select a setting item with
the
SET (BS2)
button.
Select a check item with
the
SET (BS2)
button.
Setting condition
(Contents) display
Setting mode 1
(Initial condition)
MODE
OFF
H1P
Press the
MODE (BS1)
button for more
than 5 seconds.
MODE
ON
H1P
H1P
Blinking
MODE
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...