Troubleshooting by Error Codes
SiUS281811EA
222
Part 6 Service Diagnosis
Note(s)
Reference
Troubleshooting
∗
1. Check the following connectors.
CHECK 16
Refer to page 306.
Properly connect the connector.
NO
Is the
connector properly
connected to the indoor
unit main PCB?
(
1)
Replace the fan motor.
NO
YES
By
disconnecting the
connector, the fan can be
lightly rotated by
hand.
Remove the foreign matter.
YES
YES
NO
Are there
any foreign matter
around the fan?
YES
NO
Is the
resistance between
the pins less than the
judgment criteria?
Replace the indoor unit main
PCB (A1P).
CHECK 16
Disconnect the connector
from the fan motor, and then
make measurement of
resistance between pins.
Turn OFF the power
supply, and then wait for
a period of 10 minutes.
Replace the fan motor and the
indoor unit main PCB (A1P).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Model
Connector
FCQ-TA
X20A, Relay connector
FAQ-TA
X20A
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...