![background image](http://html1.mh-extra.com/html/daikin/skyair-rzr-ta-series/skyair-rzr-ta-series_service-manual_3918999169.webp)
SiUS281811EA
Field Setting from Remote Controller
Part 5 Field Settings and Test Operation
163
Note(s)
1.5.22 Swing Pattern Settings
(For units with an infrared floor sensor)
Set the flap operation in swing mode.
With the factory swing, flaps facing each other are synchronized to operate, and flaps placed side
by side are set to swing in an opposite direction to agitate airflow to reduce temperature irregularity.
Conventional swing operation (all direction synchronized swing) can be set onsite.
: Factory setting
1.5.23 Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
When the model FCQ-TA is attached with a closing member kit, set the Second Code No. to
02
or
03
.
1.5.24 External Static Pressure Settings
Make external static pressure setting automatically using automatic airflow adjustment, or manually
using external static pressure settings.
Make sure that 11 (21)-7 (Airflow adjustment) is set to
01
(OFF).
Mode
No.
First Code
No.
Second Code
No.
Contents
13 (23)
2
01
All direction synchronized swing
02
—
03
Facing swing
FCQ-TA, FAQ-TA
: Factory setting
Mode
No.
First Code
No.
Second Code
No.
Contents
13 (23)
4
01
Draft prevention (Upward)
02
Standard
03
Ceiling soiling prevention (Downward)
FBQ-P
: Factory setting
Mode No.
First Code No.
Second Code No.
Contents
13 (23)
6
02
50 Pa (0.20 inWG)
03
60 Pa (0.24 inWG)
04
70 Pa (0.28 inWG)
05
80 Pa (0.32 inWG)
06
90 Pa (0.36 inWG)
07
100 Pa (0.40 inWG)
08
110 Pa (0.44 inWG)
09
120 Pa (0.48 inWG)
10
130 Pa (0.52 inWG)
11
140 Pa (0.56 inWG)
12
150 Pa (0.60 inWG)
13
160 Pa (0.64 inWG)
14
180 Pa (0.72 inWG)
15
200 Pa (0.80 inWG)
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...