Troubleshooting by Error Codes
SiUS281811EA
216
Part 6 Service Diagnosis
4.4 External
Protection
Device Abnormality (Except FTQ-TA)
Error Code
A0
Applicable
Models
All indoor models (except FTQ-TA)
Method of Error
Detection
Detect open or short circuit between external input terminals in indoor unit.
Error Decision
Conditions
When an open circuit occurs between external input terminals with the remote controller set for
external ON/OFF terminal.
Supposed
Causes
Activation of external protection device
Improper field setting
Defective indoor unit PCB
Troubleshooting
Activation of external protection
device.
External
protection
device is connected to
terminals T1 and T2 of the
indoor unit terminal
block.
Replace the indoor unit main PCB
(A1P).
YES
Change the second code No. to
01
or
02
.
ON/OFF
input from
outside (mode No.
12, first code No. 1) has
been set to external
protection device input
(second code No.
03) by remote
controller.
YES
NO
Check the setting state of the
ON/OFF input by remote
controller.
NO
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...