SiUS281811EA
Centralized Control Group No. Setting
Part 3 Remote Controller
97
5.2 Wireless
Remote
Controller
Group No. setting by wireless remote controller for centralized control
1. When in the normal mode, press
INSPECTION/TEST
button for 4 seconds or more to enter field
setting mode.
2. Set mode No. 00 with
MODE
button.
3. Set the group No. for each group with
UP
button or
DOWN
button.
4. Enter the selected group numbers by pressing
RESERVE
button.
5. Press
INSPECTION/TEST
button and return to the normal mode
UP
button
DOWN
button
MODE
button
RESERVE
button
Mode No.
Field setting mode
Group No.
INSPECTION/TEST
button