Specifications
SiUS281811EA
60
Part 1 General Information
Model
name
Indoor unit
FBQ30PVJU
FBQ36PVJU
Outdoor unit
RZQ30TAVJUA
RZQ36TAVJUA
Power supply
1 phase, 208/230 V, 60 Hz
1 phase, 208/230 V, 60 Hz
1
4 Cooling capacity
Btu/h
(kW)
30,000 (8.8)
36,000 (10.6)
2
4 Heating capacity
Btu/h
(kW)
34,000 (10.0)
40,000 (11.7)
3
4 Heating capacity
Btu/h
(kW)
22,000 (6.4)
21,000 (6.2)
SEER (Rated)
16.0
17.5
EER (Rated)
Btu/h
∙
W
10.5
11.1
HSPF (Rated)
9.2
9.1
Indoor unit
FBQ30PVJU
FBQ36PVJU
Casing color
Galvanized steel plate
Galvanized steel plate
Dimensions: (H×W×D)
in (mm)
11–13/16 × 39–3/8 × 27–9/16 (300 × 1,000 × 700)
11–13/16 × 55–1/8 × 27–9/16 (300 × 1,400 × 700)
Coil
Type
Cross fin coil
Cross fin coil
Rows×Stages×FPI
3 × 16 × 15
3 × 16 × 15
Face area
ft² (m
2
)
2.68 (0.249)
4.12 (0.383)
Fan
Model
—
—
Type
Sirocco fan
Sirocco fan
Motor output
W
350
350
Airflow rate (HH/H/L)
cfm
(m
3
/min)
882/794/706 (25.0/22.0/20.0)
1,130/953/812 (32.0/27.0/23.0)
External static
pressure
inH
2
O
(Pa)
Standard 0.40 <0.80-0.20> (100 <200-50>)
5
Standard 0.40 <0.80-0.20> (100 <200-50>)
5
Sound pressure level (HH/H/L)
dB(A)
43.0/41.0/39.0
43.0/41.0/39.0
Air filter
—
6
—
6
Weight
lbs (kg)
80 (36)
102 (46)
Connecting
Pipes
Liquid Pipe
in (mm)
φ
3/8 (
φ
9.5) (Flare connection)
φ
3/8 (
φ
9.5) (Flare connection)
Gas Pipe
in (mm)
φ
5/8 (
φ
15.9) (Flare connection)
φ
5/8 (
φ
15.9) (Flare connection)
Drain Pipe
in (mm)
VP25 (External dia. 1–1/4 (32), internal dia. 1 (26))
VP25 (External dia. 1–1/4 (32), internal dia. 1 (26))
Remote controller
(option)
Wired
BRC1E73, BRC2A71
BRC1E73, BRC2A71
Wireless
BRC4C82, BRC082A43
BRC4C82, BRC082A43
Outdoor unit
RZQ30TAVJUA
RZQ36TAVJUA
Casing color
Ivory white
Ivory white
Dimensions: (H×W×D)
in (mm)
52–15/16 × 35–7/16 × 12–5/8 (1,345 × 900 × 320)
52–15/16 × 35–7/16 × 12–5/8 (1,345 × 900 × 320)
Coil
Type
Cross fin coil
Cross fin coil
Rows×Stages×FPI
2 × 60 × 19
2 × 60 × 19
Face area
ft² (m
2
)
12.2 (1.134)
12.2 (1.134)
Compressor
Model
2YC90FXD#A
2YC90FXD#A
Type
Hermetically sealed swing type
Hermetically sealed swing type
Motor output
kW
3.5
3.5
Fan
Model
P47N
P47N
Type
Propeller fan
Propeller fan
Motor output
W
70 × 2
70 × 2
Airflow rate
cfm
(m
3
/min)
3,741 (106)
3,741 (106)
Weight
lbs (kg)
225 (102)
225 (102)
Sound pressure level
dB(A)
57
57
Connecting
Pipes
Liquid Pipe
in (mm)
φ
3/8 (
φ
9.5) (Flare connection)
φ
3/8 (
φ
9.5) (Flare connection)
Gas Pipe
in (mm)
φ
5/8 (
φ
15.9) (Flare connection)
φ
5/8 (
φ
15.9) (Flare connection)
Drain Pipe
in (mm)
φ
1 (
φ
26) (Hole)
φ
1 (
φ
26) (Hole)
Safety devices
High pressure switch, Outdoor fan driver overload
protector, Inverter overload protector, Fusible plugs, Fuse
High pressure switch, Outdoor fan driver overload
protector, Inverter overload protector, Fusible plugs, Fuse
Capacity Control
%
14-100
14-100
Refrigerant control
Electronic expansion valve
Electronic expansion valve
Ref.
piping
Standard length
ft (m)
25 (7.6)
25 (7.6)
Max. length
ft (m)
230 (70)
230 (70)
Max. height
difference
ft (m)
98 (30)
98 (30)
Refrigerant
Model
R-410A
R-410A
Charge
lbs (kg)
7.9 (3.6)
7.9 (3.6)
Ref. oil
Model
DAPHNE FVC50K
DAPHNE FVC50K
Charge
L
1.52
1.52
Drawing
No
Specification
C: 4D126352
C: 4D126352
Sound (indoor)
C: 4D075280
C: 4D075281
Sound (outdoor)
C: 4D101949D
C: 4D101949D
Notes:
1 Indoor temp.: 80°FDB (26.7°CDB), 67°FWB (19.4°CWB) / Outdoor temp.: 95°FDB (35.0°CDB) / Equivalent piping length: 25 ft (7.6 m), level difference: 0 ft (0 m).
2 Indoor temp.: 70°FDB (21.1°CDB) / Outdoor temp.: 47°FDB (8.3°CDB), 43°FWB (6.1°CWB) / Equivalent piping length: 25 ft (7.6 m), level difference: 0 ft (0 m).
3 Indoor temp.: 70°FDB (21.1°CDB) / Outdoor temp.: 17°FDB (
−
8.3°CDB), 15°FWB (
−
9.4°CWB) / Equivalent piping length: 25 ft (7.6 m), level difference: 0 ft (0 m).
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 External static pressure is changeable in 14 stages within the < > range by remote controller.
6 Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity method) 50% or more.
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...