Protection Control
SiUS281811EA
118
Part 4 Functions and Control
Heating operation
4.2 Low Pressure Protection Control
This low pressure protection control is used to protect compressors against the transient decrease
of low pressure.
Pe: Low pressure sensor detection value
Cooling
operation
High pressure drop
Pc
> 3.04 MPa (441 psi)
After 10 sec.
Pc > 3.04 MPa (441 psi)
Pc < 2.94 MPa (426 psi)
Pc > 3.64 MPa (528 psi)
Current step maintained
After 60 sec.
High pressure not limited
High pressure limited
Compressor upper limit
frequency: 1-step up from
current compressor frequency
Compressor upper limit
frequency: 1-step down from
current compressor frequency
When occurring 10 times within 60
minutes, high pressure switch is activated
without high pressure standby, thus
outputting the error code
E3
.
Pc
< 2.89 MPa (419 psi)
High pressure
standby
Pe < 0.25 MPa
(36.3 psi)
36 Hz Unload
Pe > 0.39 MPa
(56.6 psi)
Pe < 0.07 MPa
(10.2 psi)
Low pressure not limited
Pe < 0.15 MPa
(21.8 psi)
Pe > 0.30 MPa
(43.5 psi)
Hot gas bypass valve: OFF
Hot gas bypass valve: ON
When occurring 3 times within 30 minutes,
the error code
E4
is output.
Low pressure
standby
Low pressure
limited
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...