4.4 Power Quality Parameters
4.4.1 Unbalance
The PMC-592 measures the Voltage and Current Unbalances based on the following:
100%
V
Unbalance
Voltage
1
2
V
100%
I
I
Unbalance
Current
1
2
Where
U₁ is Positive Sequence Voltage and U₂ is Negative Sequence Voltage.
and
I₁ is Positive Sequence Current and I₂ is Negative Sequence Current.
Under 1P3W wiring mode, the calculation method is listed below:
100%
Unbalance
Voltage
Ub)
(Ua
|
Ub
-
Ua
|
100%
Unbalance
Current
Ib)
(Ia
|
Ib
-
Ia
|
4.4.2 Harmonics
The PMC-592 provides the following Harmonic parameters:
Mains-I/II Inputs
U & I THD/TOHD/TEHD
U & I Individual Harmonics up to the 31st order
Current K-factor
Current TDD, TODD and TEDD since Firmware Version V1.00.05
U & I Crest Factor since Firmware V1.00.05
Branch Inputs
Current THD
All Harmonic parameters are available through communications, the built-in Web Interface and the
optional HMI Display.
The following equations illustrate how to calculate the individual harmonic distortion:
Fundamental Method:
Voltage K
th
Harmonic Distortion=
100%
1
K
V
V
Current K
th
Harmonic Distortion=
100%
I
I
1
k
Where
V
1
/ I
1
are the Fundamental Voltage/Current RMS and
V
k
/ I
k
is the k
th
Harmonic Voltage/Current RMS
The PMC-592 provides the following Harmonic measurements:
Mains-I
Mains-II
Branch
Harmonics-Voltage
Uan/Ubn/Ucn THD (WYE)
Uab/Ubc/Uca THD (Delta)
Uan/Ubn/Ucn THD (WYE)
Uab/Ubc/Uca THD (Delta)
SM1 to SM84 THD
Uan/Ubn/Ucn TEHD (WYE)
Uab/Ubc/Uca TEHD (Delta)
Uan/Ubn/Ucn TEHD (WYE)
Uab/Ubc/Uca TEHD (Delta)
Uan/Ubn/Ucn TOHD (WYE)
Uab/Ubc/Uca TOHD (Delta)
Uan/Ubn/Ucn TOHD (WYE)
Uab/Ubc/Uca TOHD (Delta)
Uan/Ubn/Ucn Crest-Factor
Uan/Ubn/Ucn Crest-Factor
Uan/Ubn/Ucn HD02 (WYE)
Uab/Ubc/Uca HD02 (Delta)
Uan/Ubn/Ucn HD02 (WYE)
Uab/Ubc/Uca HD02 (Delta)