150
CET Electric Technology
5.8.11 Data Recorder Setup
The Data Recorder Setup registers have been added since Firmware V1.00.04 and Protocol V1.2.
Register
Property
Description
Format
Range/Options/Default*
8250
RW
DR #1
Trigged Mode
1
UINT16
0=Disabled
1=Triggered by Setup Parameter*
8251
RW
Recording Mode
2
UINT16
0=Stop-When-Full, 1=First In First Out*
8252
RW
Recording Depth
3
UINT16
0 to 65535*
8253
RW
Recording Interval
UINT32
60 to 345600s, 900*
8255
RW
Recording Offset
4
UINT16
0* to 43200s
8256
RW
Parameters Number
5
UINT16
0* to 64
8257
RW
Parameter1
UINT16
See Appendix B – Data Recorder Parameter
8258
RW
Parameter2
UINT16
8259
RW
Parameter3
UINT16
…
…
UINT16
8320
RW
Parameter64
UINT16
8321~8391
RW
DR #2
UINT16
Please refer to DR #1
8392~8462
…
DR #3
UINT16
8463~8533
RW
DR #4
UINT16
8534~8604
RW
DR #5
UINT16
8605
RW
DR #6
Trigged Mode
1
UINT16
0=Disabled*
1=Triggered by Setup Parameter
8606
RW
Recording Mode
2
UINT16
0=Stop-When-Full, 1=First In First Out*
8607
RW
Recording Depth
3
UINT16
0 to 65535*
8608
RW
Recording Interval
UINT32
60 to 345600s, 900*
8610
RW
Recording Offset
4
UINT16
0* to 43200s
8611
RW
Parameters Number
5
UINT16
0* to 64
8612
RW
Parameter1
UINT16
See Appendix B – Data Recorder Parameter
8613
RW
Parameter2
UINT16
8614
RW
Parameter3
UINT16
…
…
UINT16
8675
RW
Parameter64
UINT16
8676~8746
RW
DR #7
UINT16
Please refer to DR #6
8747~8817
RW
DR #8
UINT16
8818~8888
RW
DR #9
UINT16
8889~8959
RW
DR #10
UINT16
Table 5-103 DR Parameter Setup
5.9 Time Registers
There
are
two
sets
of
Time
registers
supported
by
the
PMC-592
-
Year/Month/Day/Hour/Minute/Second (Register # 60000 to 60004) and UTC Time (Reg. # 9000 to 9004).
When sending time to the PMC-592 over Modbus communications, care should be taken to only write
one of the two Time register sets. All registers within a Time register set must be written in a single
transaction. If registers 60000 to 60004 are being written to at the same time, both Time register sets
will be updated to reflect the new time specified in the UTC Time register set (60004) and the time
specified in registers 60000-60002 will be ignored. Writing to the Millisecond register (60003) is optional
during a Time Set operation. When broadcasting time, the function code must be set to 0x10 (Pre-set
Multiple Registers). Incorrect date or time values will be rejected by the meter.
Register
Property
Description
Format
Note
60000
9000
RW
High-order Byte: Year
UINT16
0-38 (Year-2000)
Low-order Byte: Month
1 to 12
60001
9001
RW
High-order Byte: Day
UINT16
1 to 31
Low-order Byte: Hour
0 to 23
60002
9002
RW
High-order Byte: Minute
UINT16
0 to 59
Low-order Byte: Second
0 to 59
60003
9003
RW
Millisecond
UINT16
0 to 999
60004
9004
RW
UTC Time
UINT32
0x386D4380 to 0x 7FE8177F
The corresponding time is
2000.01.01 00:00:00 to