137
CET Electric Technology
6)
Self-Read Time
is applied to Max Demand Log and Max/Min Log. There are two types of
Self-Read Time
:
A zero value indicates that the transfer will happen at 00:00 of the first day of every month.
A non-zero value indicates that the transfer will happen at a specific time based on the formula [Hour+Day*100]
where 0≤Hour≤23 and 1≤Day≤28. For example, the value 2812 means that the Max Demand of Current Month will
be transferred to the Max Demand of Last Month register at 12:00pm on the 28th day of each month.
7)
Phase x Color
used to display waveform by each phase on the Web Interface or HMI. When the wiring mode is Delta, Uab,
Ubc and Uca corresponds to Phase A, Phase B and Phase C, respectively.
Code
Color
Code
Color
Code
Color
1
Brown
4
Yellow
7
Gray
2
Red
5
Green
8
Black
3
Orange
6
Blue
Table 5-53 Phase Color
8)
If the PMC-592 isn’t equipped with the optional DI3 and DI4, the DI3 and DI4 Debounce registers will be reserved.
9)
The value of [PT Primary/PT Secondary] cannot exceed 10000.
10)
The
Branch
CT’s Mains
is only meaningful when the
Panel Mode
is set to
Custom
. The table below illustrates the details
of the
Branch CT’s Mains
with 0 and 1 meaning Mains-I and Mains-II, respectively.
Bit
Bit 3
Bit 2
Bit 1
Bit 0
Branch
Branch D
Branch C
Branch B
Branch A
Table 5-54 Branch CT’s Mains (Reg. # 6047)
11)
The table below illustrates the relationship between Tariff and DI status. Only one DI can be set as a Tariff Switch.
Tariff Switch Mode
DIx Status
Tariff
Disabled
None
None
DIx
Inactive
T1
Active
T2
Table 5-55 Tariff Switch Mode
5.8.2 Communications Setup
Register
Property
Description
Format
Range/Note/Default*
6240
RW
Port 1 unit ID
UINT16
1 to 247, 100*
6241
RW
Port 1 Baud rate
UINT16
0 = 1200, 1 = 2400, 2 = 4800,
3 = 9600, 4 = 19200, 5 = 38400*
6242
RW
Port 1 Configuration
UINT16
0 = 8N2, 1 = 8O1, 2 = 8E1*
3 = 8N1, 4 = 8O2, 5 = 8E2
6243
RW
Port 2 unit ID
UINT16
1 to 247, 101*
6244
RW
Port 2 Baud rate
UINT16
0 = 1200, 1 = 2400, 2 = 4800
3 = 9600, 4 = 19200, 5 = 38400*
6245
RW
Port 2 Configuration
UINT16
0 = 8N2, 1 = 8O1, 2 = 8E1*
3 = 8N1, 4 = 8O2, 5 = 8E2
6246
RW
IP Address(H)
UINT16
If the IP Address is 192.168.0.100,
write “0xC0A80064” to this register.
(Default = 192.168.0.100)
6247
RW
IP Address(L)
UINT16
6248
RW
Subnet mask(H)
UINT16
If the Subnet Mask is 255.255.255.0,
write “0xFFFFFF00” to this register.
(Default = 255.255.255.0)
6249
RW
Subnet mask(L)
UINT16
6250
RW
Gateway Address(H)
UINT16
If the IP Address is 192.168.0.1, write
“0xC0A80201” to this register.
(Default = 192.168.2.1)
6251
RW
Gateway Address(L)
UINT16
6252
RW
SNTP Enable
UINT16
0 = Disabled*, 1 = Enabled
6253
RW
SNTP Time Sync. Interval
1
UINT16
10 to 1440 (min), 60*
6254
RW
SNTP Server IP Address (H)
UINT16
If address is 192.168.0.100, write
“0xC0A80064” to this register
(Default = 192.168.0.100)
6255
RW
SNTP Server IP Address (L)
UINT16
6256
RW
SMTP Server IP Address (H)
UINT16
If address is 191.0.0.6, write
“0XBF000006” to this register
(Default = 191.0.0.6)
6257
RW
SMTP Server IP Address (L)
UINT16
6258-6297
RW
SMTP Sender Username
UINT16X40
See Note (2)
6298-6337
RW
SMTP Login Password
UINT16X40
See Note (3)
6338-6377
RW
SMTP Receiver Email Address
UINT16X40
See Note (4)
6378
RW
TRAP Event Subscription
5
Bitmap
0* to 31
6379
RW
TRAP Event Subscriber IP Address (H)
UINT16
0*
6380
RW
TRAP Event Subscriber IP Address (L)
UINT16