140
CET Electric Technology
6445
RW
I Demand HH Alarm Threshold
UINT16
0* to 1000 (x0.1)
6446
RW
I Demand HH Alarm Time Delay
UINT16
0* to 9999 (s)
6447
RW
I Demand H Alarm Threshold
UINT16
0* to 1000 (x0.1)
6448
RW
I Demand H Alarm Time Delay
UINT16
0* to 9999 (s)
6449
RW
I Demand L Alarm Threshold
UINT16
0* to 1000 (x0.1)
6450
RW
I Demand L Alarm Time Delay
UINT16
0* to 9999 (s)
6451
RW
I Demand LL Alarm Threshold
UINT16
0* to 1000 (x0.1)
6452
RW
I Demand LL Alarm Time Delay
UINT16
0* to 9999 (s)
6453
RW
Power Demand Alarm Enable
6
Bitmap
0 = Disabled*, 1 = Enabled
6454
RW
kW Total Demand H Alarm Threshold
UINT16
0* to 1000 (x0.1)
6455
RW
kW Total Demand H Alarm Time Delay
UINT16
0* to 9999 (s)
6456
RW
kW Total Demand L Alarm Threshold
UINT16
0* to 1000 (x0.1)
6457
RW
kW Total Demand L Alarm Time Delay
UINT16
0* to 9999 (s)
6458
RW
kvar Total Demand H Alarm Threshold
UINT16
0* to 1000 (x0.1)
6459
RW
kvar Total Demand H Alarm Time Delay
UINT16
0* to 9999 (s)
6460
RW
kvar Total Demand L Alarm Threshold
UINT16
0* to 1000 (x0.1)
6461
RW
kvar Total Demand L Alarm Time Delay
UINT16
0* to 9999 (s)
6462
RW
kVA Total Demand H Alarm Threshold
UINT16
0* to 1000 (x0.1)
6463
RW
kVA Total Demand H Alarm Time Delay
UINT16
0* to 9999 (s)
6464
RW
kVA Total Demand L Alarm Threshold
UINT16
0* to 1000(x0.1)
6465
RW
kVA Total Demand L Alarm Time Delay
UINT16
0* to 9999 (s)
6466
RW
RTD1 HH Alarm Threshold
UINT16
0* to 200
6467
RW
RTD1 HH Alarm Time Delay
UINT16
0* to 9999 (s)
6468
RW
RTD1 H Alarm Threshold
UINT16
0* to 200
6469
RW
RTD1 H Alarm Time Delay
UINT16
0* to 9999 (s)
6470
RW
RTD2 HH Alarm Threshold
UINT16
0* to 200
6471
RW
RTD2 HH Alarm Time Delay
UINT16
0* to 9999 (s)
6472
RW
RTD2 H Alarm Threshold
UINT16
0* to 200
6473
RW
RTD2 H Alarm Time Delay
UINT16
0* to 9999 (s)
6474
RW
I Unbalance Alarm Enable
8
Bitmap
0 = Disabled*, 1 = Enabled
6475
RW
I Unbalance H Alarm Threshold
UINT16
0* to 1000 (x0.1%)
6476
RW
I Unbalance H Alarm Time Delay
UINT16
0* to 9999 (s)
6477
RW
U Unbalance Alarm Enable
8
Bitmap
0 = Disabled*, 1 = Enabled
6478
RW
U Unbalance H Alarm Threshold
UINT16
0* to 1000 (x0.1%)
6479
RW
U Unbalance H Alarm Time Delay
UINT16
0* to 9999 (s)
6480
RW
Harmonic Distortion Alarm Enable
9
Bitmap
0 = Disabled*, 1 = Enabled
6481
RW
THD H Alarm Threshold
UINT16
0* to 1000 (x0.1%)
6482
RW
THD H Alarm Time Delay
UINT16
0* to 9999 (s)
6483
RW
TOHD H Alarm Threshold
UINT16
0* to 1000 (x0.1%)
6484
RW
TOHD H Alarm Time Delay
UINT16
0* to 9999 (s)
6485
RW
TEHD H Alarm Threshold
UINT16
0* to 1000 (x0.1%)
6486
RW
TEHD H Alarm Time Delay
UINT16
0* to 9999 (s)
6487
RW
DI1 Alarm Configuration
UINT16
0 = Disabled
1 = DI1 Open Trigger
2 = DI1 Closed Trigger
6488
RW
DI1 Alarm Time Delay
UINT16
0* to 9999 (s)
6489
RW
DI2 Alarm Configuration
UINT16
0* = Disabled
1 = DI2 Open Trigger
2 = DI2 Closed Trigger
6490
RW
DI2 Alarm Time Delay
UINT16
0* to 9999 (s)
6491
RW
Dip/Swell Alarm Enable
#10
Bitmap
0 = Disabled, 1 = Enabled*
6492
RW
Swell Alarm Threshold
#
UINT16
101% to 200%, 110%*
6493
RW
Dip Alarm Threshold
#
UINT16
1% to 99%, 90%*
6494
RW
Interruption Alarm Threshold
#
UINT16
0% to 50%, 10%*
6495
RW
Swell Hysteresis
#
UINT16
0 to 1000 (x0.1%), 20*
6496
RW
Dip Hysteresis
#
UINT16
0 to 1000 (x0.1%), 20*
6497
RW
Interruption Hysteresis
#
UINT16
0 to 1000 (x0.1%), 20*
6498
RW
Phase Reversal Alarm Enable
#11
Bitmap
0 = Disabled*, 1 = Enabled
6499
RW
Phase Loss Alarm Enable
#12
Bitmap
0 = Disabled*, 1 = Enabled
6500
RW
Phase Loss Alarm Time Delay
#
UINT16
0 to 9999(s), 10s*
6501
RW
DI3~ Alarm Configuration
13
UINT16
0 = Disabled*
1 = DI3 Open Trigger
2 = DI3 Closed Trigger
6502
RW
DI3~ Alarm Time Delay
13
UINT16
0* to 9999 (s)
6503
RW
DI4~ Alarm Configuration
13
UINT16
0 = Disabled*
1 = DI4 Open Trigger