60
CET Electric Technology
Parameter
Description
Value
Device Name
Specifies the device name.
Default: PMC-592 MCPM
Mains-I Name
Specifies the Mains-I panel name.
Default: MCPM Panel #1
Mains-II Name
Specifies the Mains-II panel name.
Default: MCPM Panel #2
Table 3-12 Panel Name Setup Description
Figure 3-28 Panel Name Setup Interface
3.2.4.5.3 Branch Setup
Click on
Branch Setup
on the left-hand pane and the following screen appears on the right-hand pane
where the following parameters can be changed:
CT Strip Installation Mode
,
Installation Direction
,
CT
Phase
(Voltage Phase),
CT Type
,
CT Polarity
,
CT Ratio
and
Branch Labels
. Click
Submit
to save your
changes or
Cancel
to cancel your changes.
Figure 3-29 Branch Setup Interface
Parameter
Description
Options/Default*
CT Strip Installation
Specifies the CT Strip Installation Mode. Please refer to Section
2.4.3 Branch Circuit Wiring
and Sub Meter Assignment
for more
information.
Sequential Mode
Cross-over Mode
Direction
Specifies the CT Strip Installation Direction. Please refer to
Section
2.4.3 Branch Circuit Wiring
and Sub Meter Assignment
for more information.
Top
Bottom
Batch Setup
CT Phase
(Changed from
Branch Setup
since
Firmware V1.00.10)
Specifies the
CT Phase
(Voltage Phase) for each Branch Circuit of
a CT Strip by batch with respect to the Mains Inputs (Mains-I/II)
according to the
Panel Mode
setting. This batch setup only
supports the Phase pairing of the Branch CTs with the line-to-
neutral voltages. If the
Wiring Mode
for Mains-I/II is Delta, the
CT Phase
for each Branch CT must be configured individually.
------ (Not Used)
Standard (A/B/C/A…)
Reversed (C/B/A/C…)
1P3W (A/B/A/B…)
Phase A (Ua)
Phase B (Ub)
Phase C (Uc)
CT Type^
Specifies the CT Type, Solid-Core or Split-Core.
------ (Not Used)