139
CET Electric Technology
6057-6569
0x20
<Null>
Table 5-59 ASCII Encoding of “PMC-592”
5.8.4 Breakers Rating Setup
Register
Property
Description
Format
Range/Default*
6150
RW
Mains-I Breaker Rating
UINT16
1 to 10,000A
500A*
6151
RW
Mains-I I4 Current Rating
UINT16
6152
RW
Mains-II Breaker Rating
UINT16
6153
RW
Mains-II I4 Current Rating
UINT16
6154
RW
SM1 Breaker Rating
UINT16
1 to 10,000A
60A*
6155
RW
SM2 Breaker Rating
UINT16
….
….
6237
RW
SM84 Breaker Rating
UINT16
Table 5-60 Breaker Rating Setup Register
5.8.5 Alarm Setup
Register
Property
Description
Format
Range/Options/Default*
6390
RW
Universal Hysteresis
1
UINT16
0 to 100 (x0.1%), 20*
6391
RW
Current Alarm ON Threshold
2
UINT16
0 to 100 (x0.1%), 50*
6392
RW
Current Alarm ON Time Delay
UINT16
0 to 9999 (s), 10s*
6393
RW
Current Alarm OFF Time Delay
UINT16
0 to 9999 (s), 30s*
6394
RW
Current OFF Alarm Enable^
UINT16
0=Disabled*, 1=Enabled
6403
RW
Current Alarm Enable
3
Bitmap
Note 3
6404
RW
Current HH Alarm Threshold
UINT16
0 to 1000, 800*
6405
RW
Current HH Alarm Time Delay
UINT16
0 to 9999 (s), 10s*
6406
RW
Current H Alarm Threshold
UINT16
0 to 1000, 600*
6407
RW
Current H Alarm Time Delay
UINT16
0 to 9999 (s), 10s*
6408
RW
Current L Alarm Threshold
UINT16
0* to 1000
6409
RW
Current L Alarm Time Delay
UINT16
0* to 9999 (s)
6410
RW
Current LL Alarm Threshold
UINT16
0* to 1000
6411
RW
Current LL Alarm Time Delay
UINT16
0* to 9999 (s)
6412
RW
ULN Alarm Enable
4
Bitmap
0 = Disabled*, 1 = Enabled
6413
RW
ULN H Alarm Threshold
UINT16
0* to 3000 (x0.1)
6414
RW
ULN H Alarm Time Delay
UINT16
0* to 9999 (s)
6415
RW
ULN L Alarm Threshold
UINT16
0* to 3000 (x0.1)
6416
RW
ULN L Alarm Time Delay
UINT16
0* to 9999 (s)
6417
RW
ULL Alarm Enable
5
Bitmap
0 = Disabled*, 1 = Enabled
6418
RW
ULL H Alarm Threshold
UINT16
0* to 5000 (x0.1)
6419
RW
ULL H Alarm Time Delay
UINT16
0* to 9999 (s)
6420
RW
ULL L Alarm Threshold
UINT16
0* to 5000 (x0.1)
6421
RW
ULL L Alarm Time Delay
UINT16
0* to 9999 (s)
6422
RW
Power Alarm Enable
6
Bitmap
0 = Disabled*, 1 = Enabled
6423
RW
kW Total H Alarm Threshold
7
UINT16
0* to 1000(x0.1)
6424
RW
kW Total H Alarm Time Delay
UINT16
0* to 9999(s)
6425
RW
kW Total L Alarm Threshold
UINT16
0* to 1000(x0.1)
6426
RW
kW Total L Alarm Time Delay
UINT16
0* to 9999(s)
6427
RW
kvar Total H Alarm Threshold
UINT16
0* to 1000(x0.1)
6428
RW
kvar Total H Alarm Time Delay
UINT16
0* to 9999(s)
6429
RW
kvar Total L Alarm Threshold
UINT16
0* to 1000(x0.1)
6430
RW
kvar Total L Alarm Time Delay
UINT16
0* to 9999(s)
6431
RW
kVA Total H Alarm Threshold
UINT16
0* to 1000(x0.1)
6432
RW
kVA Total H Alarm Time Delay
UINT16
0* to 9999(s)
6433
RW
kVA Total L Alarm Threshold
UINT16
0* to 1000(x0.1)
6434
RW
kVA Total L Alarm Time Delay
UINT16
0* to 9999(s)
6435
RW
PF Total Alarm Enable
6
Bitmap
0 = Disabled*, 1 = Enabled
6436
RW
PF Total H Alarm Threshold
UINT16
0* to 1000(x0.001)
6437
RW
PF Total H Alarm Time Delay
UINT16
0* to 9999(s)
6438
RW
PF Total L Alarm Threshold
UINT16
0* to 1000(x0.001)
6439
RW
PF Total L Alarm Time Delay
UINT16
0* to 9999(s)
6440
RW
Frequency H Alarm Threshold
UINT16
4500 to 6500*(x0.01)
6441
RW
Frequency H Alarm Time Delay
UINT16
0 to 9999(s), 10*
6442
RW
Frequency L Alarm Threshold
UINT16
4500* to 6500 (x0.01)
6443
RW
Frequency L Alarm Time Delay
UINT16
0 to 9999 (s), 10s*
6444
RW
I Demand Alarm Enable
6
Bitmap
0 = Disabled*, 1 = Enabled