104
CET Electric Technology
Mains-I and Mains-II Max/Min Parameters
Uan/Ubn/Ucn/ULN Avg.
Uab/Ubc/Uca/ULL Avg.
Ia/Ib/Ic/I Avg./In
Ia/Ib/Ic Loading %
kWa/kWb/kWc/kW Total
kvara/kvarb/kvarc/kvar Total
kVAa/kVAb/kVAc/kVA Total
PFa/PFb/PFc/PF Total
FREQ
U/I Unbalance
RTD1/RTD2
Ia THD/TOHD/TEHD
Ib THD/TOHD/TEHD
Ic THD/TOHD/TEHD
Mains-I Uan THD/TOHD/TEHD
Mains-I Ubn THD/TOHD/TEHD
Mains-I Ucn THD/TOHD/TEHD
Mains-II Uan/Uab THD/TOHD/TEHD
Mains-II Ubn/Ubc THD/TOHD/TEHD
Mains-II Ucn/Uca THD/TOHD/TEHD
SM Max/Min Parameters
1-Ø SM1 to SM84 I
2-Ø SM1 to SM42 I
3- Ø SM1 to SM28 I
1- Ø SM1 to SM84 kW
2- Ø SM1 to SM42 kW
3- Ø SM1 to SM28 kW
1- Ø SM1 to SM84 kvar
2- Ø SM1 to SM42 kvar
3- Ø SM1 to SM28 kvar
1- Ø SM1 to SM84 kVA
2- Ø SM1 to SM42 kVA
3- Ø SM1 to SM28 kVA
1- Ø SM1 to SM84 PF
2- Ø SM1 to SM42 PF
3- Ø SM1 to SM28 PF
1- Ø SM1 to SM84 Loading %
2- Ø SM1 to SM42 Loading %
3- Ø SM1 to SM28 Loading %
SM1 to SM84 ITHD
Table 4-26 Max/Min Measurements
Max/Min data can be accessed and reset through communications, the Web Interface and the optional
HMI.
4.7.3 Interval Energy Recorder (IER)
The PMC-592 provides an IER which is capable of recording the following parameters.
Mains-I kWh/kvarh Import/Export and kVAh
Mains-I T1/T2 kWh/kvarh Import/Export and kVAh since Firmware V1.00.10
Mains-II kWh/kvarh Import/Export and kVAh
Mains-II T1/T2 kWh/kvarh Import/Export and kVAh since Firmware V1.00.10
1-Ø SM1 to SM84 kWh/kvarh Import and kVAh
2-Ø SM1 to SM42 kWh/kvarh Import and kVAh
3-Ø SM1 to SM28 kWh/kvarh Import and kVAh
VM1 to VM10 kWh/kvarh Import and kVAh
VM1 to VM10 T1/T2 kWh/kvarh and kVAh since Firmware V1.00.10
The programming of the IER is supported over communications or the Web Interface. The IER provides
the following setup parameters:
Parameter
Range/Option
Default
Recording Mode
0 = Disabled / 1 = Stop-When-Full / 2 = First-In-First-Out
2
Recording Depth
0 to 10000 (entry)
10000
Recording Interval
0 = 5mins / 1 = 10mins / 2 = 15mins / 3 = 30mins / 4 = 60mins
2
Start Time
20YY/MM/DD, HH:MM:SS
Table 4-27 IER Setup Parameters
The IER is operational when the values of
Recording Mode
and
Recording Depth
are non-zero and the
current time meets or exceeds the
Start Time
.
4.7.4 Waveform Recorder (WFR)
The PMC-592’s WFR has a log capacity of 16 entries organized in a FIFO basis, with the newest log
replacing the oldest one. The WFR Log is stored in non-volatile memory and will not suffer any loss in
the event of power failure. Each Waveform Recorder can simultaneously capture 3-phase Voltage and
Current signals at a maximum resolution of 64 samples per cycles. The WFR can be triggered manually
via communications or by the following alarms if they are enabled: Dip/Swell, Interruption, Mains
Voltage, Mains Current, Mains U/I Unbalance, Harmonics, Frequency,
Power and DI. WFR is triggered
by any alarm going active, and there is no need to do any configuration. The manual trigger command