145
CET Electric Technology
Bit
Bit 6 to Bit 15
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
SMs
Reserved
Mains-II
Mains-I
SM84
SM83
SM82
SM81
Table 5-90 VM Sign Configuration 6
5.8.8 WFR Setup
5.8.8.1 WFR Setup Parameters
Register
Property
Description
Format
Range/Options/Default*
7000
RW
WFR Format
(# of Samples/Cycles x #of Cycles)
UINT16
0 = 16x600
1 = 16x300
2 = 32x300*
3 = 32x150
4 = 64x150
5 = 64x75
7001
RW
Pre-fault Cycles
1
UINT16
1 to 10*
7002
RW
Trigger Setup
2
UINT16
0~0x003F, 1*
Table 5-91 WFR Setup
Notes:
1)
Modifying the Setup Parameters of WFRx will clear the WFRx Log and reset WFRx Pointer will be reset to “0”.
2)
The following table illustrates the details of the Trigger Setup register.
Bit
6~ 15
5
4
3
2
1
0
Trigger
Setup
Reserved
DI Alarm
Freq. Alarm
Power Alarm
Unbalance &
Harmonics
U & I Alarm
Dip/Swell
Table 5-92 Trigger Setup
5.8.8.2 WFR File Structure
Register
Property
Description
Format
7500-7519
RW
File Name
1
Char
7520
RO
File Size
UINT32
7522
RW
File Offset
2
UINT32
7524
RO
Valid Byte Count
3
UINT16
7525
RO
File Data Buffer 1
4
…
File Data Buffer 244
4
Char
…
RO
7646
RO
Table 5-93 WFR Log Structure
Notes:
1)
You must read out register 7500 to register 7519 for a time to get the whole
File Name
.
Writing the path strings what you want to read in
File Name
register, and there are the following strings and XXX represents
the file number:
WFR
configuration file: COMTRADE/WXXX.cfg
WFR
data file: COMTRADE/WXXX.dat
If the WFR
File Name
are WAVE/W001.cfg and WAVE/W001.dat, and their string codes are
0x57,0x41,0x56,0x45,0x2F,0x57,0x30,0x30,0x31,0x2E,0x63,0x66,0x67
and
0x57,0x41,0x56,0x45,0x2F,0x57,0x30,0x30,0x31,0x2E,0x64,0x61,0x74 respectively.
2)
File Offset
register defines the offset of the first byte in the data buffer of the current file, it will automatically adjust the
file offset when read the
File Offset
register and it also can adjust to the specific offset by writing a relative number to
File
Offset
register.
3)
It means that the file transfer completed when the
Valid Byte Count
is 0 and
File Offset
is equivalent to the file size.
4)
File Data Buffer 1
to
File Data Buffer 244
can be up to transfer 244 bytes data every time. And you also need to read out
all data buffer for a time to get the whole data.
5.8.9 Interval Energy Recorder Setup
5.8.9.1 IER Setup
Register
Property
Description
Format
Range/Options/Default*
7100
RW
Recording Mode
UINT16
0 = Disabled
1 = Stop-When-Full
2 = First-In-First-Out*
7101
RW
Recording Depth
1
UINT16
0 to 10000*
7102
RW
Recording Interval
UINT16
0 = 5mins, 1 = 10mins
2 = 15mins*, 3 = 30mins
4 = 60mins