30
CET Electric Technology
Custom Panel Mode
Typical Wiring Application Modes:
Typical Application Modes I and II
Typical Application Mode III
Application
:
This configuration allows a single PMC-592 to monitor one or two independent PDU panels
simultaneously. Users have the flexibility to pair any Branch Input (A, B, C or D) with any Mains Input
(Mains-I/II) using any Wiring Mode.
V1 = Mains-I Voltage Inputs
I1 = Mains-I Current Inputs
V2 = Mains-II Voltage Inputs (Applicable for
Typical Application Modes II & III
)
I2 = Mains-II Current Inputs (Applicable for
Typical Application Modes II & III
)
Power Calculation:
The Branch Power calculation is associated with its voltage source. For example, the following Branch
Power calculation is applicable for
Typical Application Mode III
:
Mains-I Power = V1 × I1 (Wye, Delta or 1P3W)
Mains-II Power = V2 × I2 (Wye, Delta or 1P3W)
Branch A Power = V1 x Branch Current A
Branch B Power = V2 x Branch Current B
Branch C Power = V2 x Branch Current C
Branch D Power = V2 x Branch Current D
Applicable Alarm:
Global
Mains-I
Mains-II
Voltage-I
●
●
○
Voltage-II
●
○
●
Current/Power-I
●
●
○
Current/Power-II
●
○
●
CT Strip A/B/C/D
●
Custom
Custom
Frequency
●
○
○
DI
●
○
○
RTD
●
○
○
Table 2-5 Panel Mode Description