121
CET Electric Technology
1884
RO
1-Ø SM2 PF
INT32
….
….
2048
RO
1-Ø SM84 PF
INT32
2050
RO
2-Ø SM1 PF Total
INT32
2052
RO
2-Ø SM2 PF Total
INT32
….
….
2132
RO
2-Ø SM42 PF Total
INT32
2134
RO
3-Ø SM1 PF Total
INT32
2136
RO
3-Ø SM2 PF Total
INT32
….
….
2188
RO
3-Ø SM28 PF Total
INT32
2190
RO
1-Ø SM1 Loading Factor
UINT32
x10
%
2192
RO
1-Ø SM2 Loading Factor
UINT32
….
….
2356
RO
1-Ø SM84 Loading Factor
UINT32
2358
RO
2-Ø SM1 Loading Factor
UINT32
2360
RO
2-Ø SM2 Loading Factor
UINT32
….
….
2440
RO
2-Ø SM42 Loading Factor
UINT32
2442
RO
3-Ø SM1 Loading Factor
UINT32
2444
RO
3-Ø SM2 Loading Factor
UINT32
….
….
2496
RO
3-Ø SM28 Loading Factor
UINT32
8000
RO
SM1 Loading Status
1
UINT32
-
0 = OFF
1 = ON
8002
RO
SM2 Loading Status
1
UINT32
….
….
8166
RO
SM84 Loading Status
1
UINT32
Table 5-10 SM Measurements
Notes:
1)
When SMx Current > Current Alarm ON Threshold (Reg. # 6391), the SMx Loading Status is ON, otherwise it’s OFF.
5.3 Energy Measurements
5.3.1 Mains Energy
Register
Property
Description
Format
Scale
Unit
2500
RO
Mains-I, kWh Import
UINT32
x10
kWh
2502
RO
Mains-I, kWh Export
UINT32
2504
RO
Mains-I, kvarh Import
UINT32
x10
kvarh
2506
RO
Mains-I, kvarh Export
UINT32
2508
RO
Mains-I, kVAh
UINT32
x10
kVAh
2510
RO
Mains-II, kWh Import
UINT32
x10
kWh
2512
RO
Mains-II, kWh Export
UINT32
2514
RO
Mains-II, kvarh Import
UINT32
x10
kvarh
2516
RO
Mains-II, kvarh Export
UINT32
2518
RW
Mains-II, kVAh
UINT32
x10
kVAh
Table 5-11 Mains Energy
5.3.2 SM Energy
Register
Property
Description
Format
Scale
Unit
2520
RO
1-Ø SM1 kWh
UINT32
x10
kWh
2522
RO
1-Ø SM2 kWh
UINT32
….
….
2686
RO
1-Ø SM84 kWh
UINT32
2688
RO
2-Ø SM1 kWh
UINT32
2690
RO
2-Ø SM2 kWh
UINT32
….
….
2770
RO
2-Ø SM42 kWh
UINT32
2772
RO
3-Ø SM1 kWh
UINT32
2774
RO
3-Ø SM2 kWh
UINT32
….
….
2826
RO
3-Ø SM28 kWh
UINT32
2828
RO
1-Ø SM1 kvarh
UINT32
x10
kvarh
2830
RO
1-Ø SM2 kvarh
UINT32