148
CET Electric Technology
5.8.10.2 Clear/Reset Control
Register
Property
Description
Format
Note
7200
WO
Clear All Latched Alarms
UINT16
Writing “0xFF00” to the register clears all the
Latched Alarms
7201
WO
Clear All Alarm Counters
UINT16
Writing “0xFF00” to the register clears all the
Alarm Counters
7202
WO
Clear SOE
UINT16
Writing “0xFF00” to the register clears the
SOE Log
7203
WO
Clear Energy
1
UINT16
1) Writing “0xFFFF” to the register clears all
the Energy registers
2) Writing “0x00FF” to the register clears all
Mains Energy registers
3) Writing “0x01FF” to the register clears all
SM Energy registers
4) Writing “0x02FF” to the register clears all
VM Energy registers
7204
WO
Clear Max Demand Logs
2
UINT16
1) Writing “0xFFFF” to the register clears all
the Max Demand Logs and Max Demand Logs
of This Month
2) Writing “0x00FF” to the register
clears all Mains Max Demand Logs and Max
Demand Logs of This Month
3) Writing “0x01FF” to the register clears all
SMx Max Demand Logs and Max Demand
Logs of This Month
7205
WO
Clear Max/Min Recorder Logs
UINT16
Writing “0xFF00” to the register clears all the
Max/Min Logs
7206
WO
Clear WFR Log
UINT16
Writing “0xFF00” to the register clears all the
WFR
7207
WO
Clear IER Logs
UINT16
Writing “0xFF00” to the register clears all the
energy logs
7208
WO
Trigger WFR
UINT16
Writing “0xFF00” to the register trigger WFR
7209
WO
Voltage Phase for Sequential Mode
UINT16
Writing “0xFF00” to the register configures
the Voltage Phase for Sequential Mode
7210
WO
Voltage Phase for Cross-over Mode
UINT16
Writing “0xFF00” to the register configures
the Voltage Phase for Cross-over Mode
7211
WO
Voltage Phase 1P3W Mode
UINT16
Writing “0xFF00” to the register configures
the Voltage Phase for 1P3W Mode
7212
WO
Test Sending Email
3
UINT16
Writing “0xFF00” to the Register sends a test
Email to the specified Destination Email
address.
7213
WO
Clear DR
#
UINT16
Writing 0 to 9 to the register clears DR#1 to
DR#10, while writing “0xFF00” clears all of
the DRs
7220
WO
Clear All
4
UINT16
Writing “0xFF00” to the register clears all of
the above
7221
WO
Reset Device to Default*
UINT16
Writing “0xFF00” to the register reset all
parameters to default.
#
Available in Firmware V1.00.04 or later
* Available in Firmware V1.00.05 or later
Table 5-100 Clear/Reset Control Setup
Notes:
1)
The following table provides a detailed description of the different values that can be written to the
Clear Energy
register to
clear the different Energy registers such as Mains-I, Mains-II, SMx and VMx.
Key
Clear Energy Register Values
Description
High Order
Low Order
0
0x00
(Mains)
0x00
Clear Main-I Energy (0x0000)
0x01
Clear Main-II Energy (0x0001)
1
0x01
(SMx)
0x00
Clear 1-Ø SM1 Energy (0x0100)
0x01
Clear 1-Ø SM2 Energy (0x0101)
0x02
Clear 1-Ø SM3 Energy (0x0102)
….
….
0x53
Clear 1-Ø SM84 Energy (0x0153)
0x54
Clear 2-Ø SM1 Energy (0x0154)
0x55
Clear 2-Ø SM2 Energy (0x0155)
0x56
Clear 2-Ø SM3 Energy (0x0156)