124
CET Electric Technology
4707
RO
RTD 2 Temperature
INT16
Table 5-16 Present Temperature Demand
5.4.2 Max Demand Log
5.4.2.1 Mains Max Demand
Register
Property
Description
Format
20000-20047
RO
Historical Max Demand
See
Section 5.4.2.2
Mains Max Demand Data Structure
20048-20095
RO
Max Demand of This Month
20096-20143
RO
Max Demand of Last Month
Table 5-17 Mains Max Demand
5.4.2.2 Mains Max Demand Data Structure
Offset
Property
Description
Format
Scale
Range
+0
RO
Mains-I, Ia
MAX32U
1
x1000
A
+4
RO
Mains-I, Ib
+8
RO
Mains-I, Ic
+12
RO
Mains-I, kW Total
MAX32
2
x1000
kW
+16
RO
Mains-I, kvar Total
x1000
kvar
+20
RO
Mains-I, kVA Total
x1000
kVA
+24
RO
Mains-II, Ia
MAX32U
1
x1000
A
+28
RO
Mains-II, Ib
+32
RO
Mains-II, Ic
+36
RO
Mains-II, kW Total
MAX32
2
x1000
kW
+40
RO
Mains-II, kvar Total
x1000
kvar
+44
RO
Mains-II, kVA Total
x1000
kVA
Table 5-18 Mains Max Demand Data Structure
Notes:
1)
MAX32U
means an unsigned 32-bit Max Demand Log, the log data structure is illustrated in the following table.
Offset
Property
Description
Format
+0
RO
Record Value
UINT32
+2
RO
Record Time
UNIX Time
Table 5-19 MAX32U Max Demand Log Data Structure
2)
MAX32
means a signed 32-bit Max Demand Log, the log data structure is illustrated in the following table.
Offset
Property
Description
Format
+0
RO
Record Value
INT32
+2
RO
Record Time
UNIX Time
Table 5-20 MAX32 Max Demand Log Data Structure
5.4.2.3 SM Max Demand
Register
Property
Description
Format
20144-22607
RO
Historical Max Demand
See
Section 5.4.2.4
SM Max Demand Data Structure
22608-25071
RO
Max Demand of This Month
25072-27535
RO
Max Demand of Last Month
Table 5-21 SM Max Demand
5.4.2.4 SM Max Demand Data Structure
Offset
Property
Description
Format
Scale
Range
+0
RO
1-Ø SM1 Current
MAX32U
1
x1000
A
+4
RO
1-Ø SM2 Current
....
….
+332
RO
1-Ø SM84 Current
+336
RO
2-Ø SM1 Current
+340
RO
2-Ø SM2 Current
....
….
+500
RO
2-Ø SM42 Current
+504
RO
3-Ø SM1 Current
+508
RO
3-Ø SM2 Current
....
….